Fire and Life Safety Inspection Criteria
See EH&S fire and life safety criteria for laboratory inspections.
|
Finding Script |
Finding Description |
Risk Level |
Reference |
|---|---|---|---|
|
Are all electrical panels and electrical service equipment clear and accessible? |
Clearance of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment/panels. Clear the area to ensure proper accessibility. |
Low |
|
|
Is electrical equipment and wiring undamaged, unexposed, and protected? |
Due to electrical shock potential, electrical wiring, devices, appliances and other equipment that is improperly modified or damaged, unprotected and/or constitutes an electrical shock or fire hazard, shall be removed from service until professional repairs are made. Open junction boxes and open-wiring with live energy is prohibited. Cords shall be maintained in good condition without splices, deterioration, damage or tape repair. Cover plates are required for outlets, switches and electrical boxes. Protection for floor receptacles shall be in place to prevent damage, and in outdoor/wet/damp locations, GFCI and weather proof "in-use" UL rated cover/enclosure is required. This cover provides sealed weather protection even when cords are plugged into the receptacle. Lock Out/Tag Out procedures of the equipment may be needed until equipment is deemed safe for use by qualified professional. Contact Facilities Management to replace/repair building related condition. |
Medium |
|
|
Are all power cords and power strips rated and used appropriately (no use of cube adapters)? |
Unfused power strips and multiplug adapters (such as cube adapters) are prohibited. Extension cords cannot be daisy-chained together, be a substitute for permanent wiring (over 90 days) or be affixed to structures. Extension cords must be listed (UL) and meet the grounding and amperage requirements of the portable appliance. Extension cords also cannot be extended through walls, ceilings or floors, under doors or floor coverings, nor can the cords be subject to environmental damage or physical impact. |
Low |
|
|
Is equipment used near sinks or in wet environments protected by GFCI outlet? |
Ground-fault circuit interrupter (GFCI) protection is required for electrical equipment used within 6 feet of sinks, electrical outlets within 6 feet of sinks, and/or in wet environments. Contact Facilities Management to install or verify and label GFCI (858) 534-2930. |
Medium |
|
|
Are minimally rated ABC fire extinguishers located within 75 feet of travel in any direction and at least one within the lab space? |
The campus standard for fire extinguishers requires that there must be an ABC extinguisher located within 75 feet of travel in any direction and a minimum of one extinguisher within the lab area and must have a minimal ABC rating of 4A:60B:C. For installation or replacement of an extinguisher, contact Facilities Management. Note that specialty extinguishers, such as C02 and Class D, may be needed in addition to the ABC extinguishers but do not replace the ABC extinguisher requirement. |
Medium |
|
|
Are fire extinguishers mounted at least 4 inches above the ground but no more than 5 feet high and easily visible? |
Extinguishers must be mounted so that the bottom of the extinguisher is a minimum of 4 inches off the ground but the top of the extinguisher is not more than 5 feet high. If the extinguisher is not easily visible/found, then a "Fire Extinguisher Here" sign is required. For installation, replacement or signage for a fire extinguisher contact Facilities Management. |
Low |
|
|
Are combustible materials separated from heating devices so that ignition cannot occur? |
Combustible materials (e.g., wooden/cardboard boxes, magazine/journals, paper products, plasticware, laboratory supplies, etc.) must be separated from all heating devices so that ignition cannot occur. A combination of distance and fire proof shielding may be used according to the device manufacturer recommendations. If no manufacturer recommendations can be obtained, an adequate combination of fire proof shielding and distance must be maintained so that ignition cannot occur. Remove all combustible materials that are within this area. Note that a Hazard Control Plan (HCP) is required for labs with a furnace. |
Medium |
N/A |
|
Are emergency exits and exit pathways signed, unrestricted, and free of obstructions? |
Emergency exit doors and pathways of egress must remain unrestricted, free from obstructions and operational at all times. Remove any item that interferes with the operation, full closure, or access to exit doors. Remove items that interfere with or restrict the path of egress. Emergency exit signs must be visible, illuminated, unobstructed and pointed correctly. For repairs to the exit signs or non-functioning doors, contact Facilities Management. |
Medium |
|
|
Is the interior lab egress pathway and bay or aisleways sufficiently clear? |
A clear egress pathway is necessary in the event of an emergency. A minimum of 44 inches of clearance is required for main egress pathways. For internal lab pathways a minimum clearance of 36 inches must always be maintained (a smaller width may be allowed with Fire Marshal approval). Remove all items that interfere with minimal aisle width. |
Medium |
Laboratory Fire Safety Inspection: Corridors and Core Spaces |
|
Is the total accumulation of combustible materials excessive? |
The excessive accumulation of combustible materials (e.g., wooden/cardboard boxes, paper, plasticware, laboratory supplies, etc.) can overwhelm the building fire suppression systems and is prohibited. In addition, excessive accumulation of combustible materials creates a greater potential for fire, entrapment, and an environment where an accident may occur. Minimize excessive combustible items. |
Medium |
|
|
Are all corridors, stairwells, elevator lobbies, etc. free and clear of unauthorized materials and/or equipment? |
Unauthorized material and/or equipment that is the responsibility of the lab was stored in corridors, stairwells, elevators, lobbies etc. and red tagged by EH&S indicating the material/equipment must be removed. Storage of unauthorized materials in these areas restricts safe building evacuation and contributes to increased risk of fire load, limits effectiveness of building's fire protection systems, and limits access to critical utilities. Examples of spaces include: hallways, corridors, stairwells, elevator lobbies, mechanical core and utility rooms, loading docks, and roof areas. Remove all unauthorized materials and equipment that have been red-tagged. Contact ehsrap@ucsd.edu to request authorization to place equipment or material in a corridor. EH&S will tag authorized items to indicate approval if granted. |
Medium |
Laboratory Fire Safety Inspection: Corridors and Core Spaces |
|
Are fire extinguishers serviced annually? |
Fire extinguishers must be serviced annually by a licensed vendor. This is coordinated by Facilities Management (FM). The fire extinguisher will have an inspection tag attached with the yearly service certification stamped into the tag. To request service, or replacement of extinguishers, contact Facilities Management. |
Low |
|
|
Are fire extinguishers inspected and documented monthly? |
Fire extinguishers in the lab must be inspected monthly by laboratory personnel. See "Fire Extinguisher Inspection Checklist" page on Blink for inspection criteria. Monthly inspections are documented by initialing and dating the inspection tag attached to the fire extinguisher. To resolve this finding, provide an action plan to schedule and complete monthly inspections (e.g., set up monthly calendar reminders to complete fire extinguisher inspection). |
Low |
|
|
Is there a clearance of at least 18 inches below the height of the fire sprinkler heads or 24 inches from the ceiling in non-sprinkled areas? |
Fire code requires fire sprinklered locations to have a minimum 18 inches of clearance between a sprinkler head and anything below it. Non-sprinklered locations require 24-inch clearance from the ceiling. Remove all items obstructing this clearance requirement. |
Medium |
|
|
Is fire and life safety equipment (fire extinguisher, pull station, alarm strobe, smoke detector, etc.) present, visible, clear and accessible? |
Fire and life safety equipment is required to be maintained in designated location, visible, and accessible at all times. Any items that interfere with the operation, accessibility, or visibility of fire and life safety equipment must be removed. Examples of fire and life safety equipment include, but are not limited to, fire extinguishers, pull stations, alarm strobe, smoke detectors, etc. |
Medium |
|
|
Are ceiling tiles and walls (i.e. fire resistant barrier protections) intact, in place and uncompromised? |
Fire resistant barriers, such as fire rated walls and fire rated ceiling tiles, help prevent the spread of fire. In case of a fire, displaced ceiling tiles or holes in the fire barrier compromise adjacent rooms and floors. Fire resistive construction must be kept intact at all times. Any penetrations or modifications (e.g., holes in drywall, running cable or wires through walls, etc.) to fire resistant barriers must be reviewed and approved by Facilities Management and EH&S Fire and Life Safety. Contact Facilities Management for replacement or repair of compromised fire barriers. |
Medium |
|
|
Are laboratory materials stored in a neat, clean, and orderly manner? |
Laboratory materials (e.g., wooden/cardboard boxes, paper, plasticware, laboratory supplies, etc.) when kept in a disorderly manner can create an environment where accidents may occur. Laboratories must be kept neat, clean and orderly. Any stacked items must be stable. Minimize, reorganize, and/or remove legacy materials. |
Medium |
|
|
Are fire doors closed or able to self-close, and free of doorstops? |
Fire doors are part of the building's fire safety system. Propped-open fire doors defeat the intended function in preventing the spread of fire, fumes, or gases. Fire doors cannot be propped open and must be kept closed unless an approved means is used (such as magnetic fire door closure system). Ensure door closure mechanism is connected and fully functional. Remove any obstruction or door stops that interfere with the complete closing and latching of the fire rated door. |
Medium |
|
|
For locations that use/store flammable metals, is there a Class D fire extinguisher within 75 feet of the work/storage area? |
A Class D (flammable metals) fire extinguisher is required to be within 75 feet of the work and storage area of flammable metals. Examples of flammable metals and metal compounds are: lithium, sodium, potassium, magnesium, butyllithium, diethylzinc, and lithium aluminum hydride. Standard ABC fire extinguishers are not effective against, and should not be used, to put out a Class D fire. Flammable metals present the greatest risk when the metals are in a finely divided form (powder, dust, shavings, turnings, etc.). Once ignited, the flammable metals are very difficult to extinguish. Extinguisher needs to be mounted or affixed to a cart within a designated area. For new Class D extinguishers, contact ehsrap@ucsd.edu to coordinate with Facilities Management for yearly maintenance. Review the Flammables/Pyrophorics section of the "Chemical Storage and Inventory" Blink page and the "Fire Extinguisher Types and Maintenance" Blink page. |
High |
Questions? Contact the EH&S Research Assistance Program.