Chemical Safety Inspection Criteria
See EH&S chemical safety criteria for laboratory inspections.
|
Finding Script |
Finding Description |
Risk Level |
Reference |
|---|---|---|---|
|
Are compressed gas cylinders stored and handled properly? |
Storage and handling requirements apply to all compressed gases. Gas cylinders must be properly stored in a cool, dry, well-ventilated location with appropriate labeling and secured with non-combustible upper and lower restraints. Cap cylinders and remove regulators when transporting or when not in use. Do not store incompatible gases next to each other. Preferably restrain cylinders individually; if unavoidable, only restrain three or fewer cylinders per restraint. All UC San Diego researchers working with compressed gases must follow an approved Hazard Control Plan. |
Medium |
|
|
Are toxic or high hazard gases used/stored properly? |
Additional precautions are required for use and storage of toxic and high hazard gases. Use appropriate equipment and engineering controls when using these gases. |
High |
Refer to the Toxic or High-Hazard Gases for more information and material-specific requirements. |
|
Is your compressed gas cylinder <10 years past the last stamped hydrostatic test date on the cylinder shoulder? |
Do not keep non-corrosive compressed gases longer than 10 years from the last hydrostatic test date (usually stamped just below the neck of the cylinder) unless otherwise regulated. Any cylinder containing a corrosive gas may never be stored longer than 6 months, as they degrade over time. |
Low |
Refer to Compressed Gas Storage and Handling for details and STORE Compressed Gas Cylinders for instructions on how to request pickup of overdue tank. |
|
Is the chemical fume hood currently certified? |
Chemical fume hoods must be certified within the last 12 months. During this lab safety audit, the RAP inspector has notified EH&S to certify an out of compliance fume hood. Notify your RAP specialist when the fume hood has been certified. |
Low |
|
|
Is the chemical fume hood equipped with a properly functioning fume hood monitor? |
Chemical fume hoods must have a properly functioning fume hood monitor. If the fume hood monitor is not functioning properly (visual/audio components indicate normal operation), contact Facilities Management immediately. Stop all work in the hood and post a "Do Not Use" sign on the hood until the problem is corrected. |
Medium |
|
|
Is the chemical fume hood free of clutter, contamination, and/or otherwise used properly? |
Chemical fume hoods must be used in a safe manner. They must be free of clutter, contamination, well-lit, and keep baffles at the back of the hood unobstructed. Elevate large equipment at least two inches off the base. Keep the sash closed as much as practical and work at least six inches inside the hood. Fume hoods must be in good repair, no cracks in the sash, and not modified from original design. Ductless fume hood equipment needs to be reviewed and approved before purchase and use by the EH&S Chemical Hygiene Officer. |
Medium |
|
|
Is equipment connected to house vacuum system using a trap? |
When using a vacuum source, it is important to place a trap between the experimental apparatus and the vacuum source. For particulates, use filtration capable of efficiently trapping the particles in the size range being generated. For most aqueous or non-volatile liquids, a flask with an in-line hydrophobic filter at room temperature is adequate. For solvents and other volatile liquids, use a cold trap followed by an in-line filter flask. Filters must be replaced as needed — at a minimum, every 90 days and when there is any evidence of deficiencies (e.g., filter blockage, failure, wetness). When changing out filters, dispose of them as hazardous chemical waste. For highly reactive, corrosive or toxic gases, use a sorbent canister or scrubbing device and cannot be used with a house vacuum system. |
Medium |
Review the "Vacuum Trapping" section of General Chemical Safety Guidelines or Chemical Hygiene Plan for further details. |
|
Are less than 10 gallons of flammable liquids stored outside of flammable storage cabinets? |
No more than 10 gallons of flammable liquids may be stored outside of flammable liquid storage cabinets. Reduce inventory to appropriate limits. |
Medium |
Flammable and Combustible Liquids Container Size and Quantity Limits |
|
Are flammable liquids in excess of 1 gallon stored in appropriate metal or OSHA compliant safety containers? |
Flammable liquids in excess of one gallon must be stored in an approved container, such as a metal safety can. |
Medium |
Review Flammable and Combustible Liquids Container Size and Quantity Limits, which describes the type and maximum size of shipping/storage containers allowable based on the liquid's hazard classification. |
|
Are cold flammable liquids stored appropriately? |
Never use standard or domestic refrigerators/freezers, deli cases, or environmental rooms (cold/warm rooms) to store flammable materials. These have little to no air circulation or air exchanges and ignition sources that could ignite flammable vapors. Fridges and freezers used for cold flammable materials must be UL-listed, explosion-proof or spark-proof, and meet NFPA OSHA standards. |
High |
|
|
Are flammables liquids transferred properly? |
Observed improper transfer or lack of appropriate engineering controls, equipment, or personal protective equipment to transfer flammable liquids. Transfer flammable liquids in a high hazard room or fume hood, when possible. Wear appropriate PPE, use proper bonding/grounding techniques, and avoid contaminating either vessel during transfer. |
Medium |
Review the "Transferring material" and "Bonding and grounding" sections of Flammable and Combustible Liquids Storage Requirements : Transferring Material for details. |
|
Are flammable gases segregated from oxidizing gases? |
Flammable gas cylinders must be segregated from cylinders containing oxidizing gas by a minimum distance of 20 feet or by a noncombustible partition extending not less than 18 inches above and to the sides of the stored material. |
High |
Storing and Handling Flammable, Oxidizing and Corrosive Gases |
|
Are peroxide forming materials stored properly and tested biannually? |
Due to potential of explosion peroxide forming material has specific handling requirements. Container(s) of peroxide forming material did not have a received date, opened date, were not tested, or were stored for excessive time periods. Once opened, they must be tested biannually in January and July. To resolve this finding, provide an action plan to schedule peroxide tests (e.g., set up biannual calendar reminders to complete test in January and July). |
High |
Refer to in-depth storage and testing guidelines available in the Hazard Control Plan: Organic Peroxides. |
|
If pyrophoric materials are being used, are personnel wearing Flame Resistant lab coats and gloves? |
Flame Resistant (FR-rated) laboratory coats and gloves must be worn when working with, or adjacent to, any amount of pyrophoric materials. |
High |
See Hazard Control Plan: Pyrophoric Materials for definitions and listings of common pyrophoric materials. |
|
If using antineoplastic or other hazardous drugs, are adequate waste disposal practices in place? |
Appropriate chemical handling, administration, personal protective equipment, and waste disposal practices are required for the safe handling of antineoplastic and other hazardous drugs. For example, trace chemo/antineoplastic waste sharps and empty vials must be collected in a designated yellow waste/sharps container. |
Medium |
Review Handling Antineoplastic or Investigational New Drugs and "Antineoplastic Agents and Other Hazardous Drugs" Hazard Control Plan for guidelines. |
|
Are acutely toxic materials used and/or stored with adequate precautions? |
Acutely toxic materials must be used and stored in the lab according to the Acutely Toxic Materials Hazard Control Plan (HCP). Designated work area(s), appropriate engineering controls, storage practices, workspace decontamination and PPE need to be used, as outlined by the HCP. Use "Acutely Toxic" stickers to label storage and work areas where known acutely toxic chemicals are used. |
High |
See Hazard Control Plan: Acutely Toxic Materials for definition of acutely toxic materials. |
|
Are cryogenic liquids handled properly? |
Use appropriate engineering controls and personal protective equipment (PPE) when handling cryogenic liquids. See "Handling Cryogenic Liquids" Blink page and Hazard Control Plan (HCP) for guidelines regarding engineering controls, operational controls, transferring, appropriate containers and review lab's LHAT for required PPE (splash protection, face shield, insulated gloves, etc.) |
Medium |
|
|
Is perchloric acid used and stored with adequate precautions? |
Perchloric acid must be used and stored in the lab with adequate precautions. Segregate perchloric acid from other chemicals and implement procedures for its safe use and disposal according to the Handling Perchloric Acid guidelines and Hazard Control Plan. A washdown type of fume hood must be used when heating or evaporating perchloric acid (NOT a regular fume hood) due to potential explosion hazard. Accumulation of perchlorates in the regular fume hood or the associated duct work can make servicing the hood dangerous as well. |
High |
|
|
Is hydrofluoric acid used and stored with adequate precautions? |
Hydrofluoric Acid (HF) must be used and stored in accordance with the HF Hazard Control Plan (HCP). Requirements include: labs MUST have unexpired calcium gluconate gel readily accessible in first aid kit, label the work area with "HF Use Area," NEVER store in glass containers, and consult Chemical Hygiene Officer (CHO) for initial experimental setup review, if work involves large quantities, or heating. |
High |
|
|
Is picric acid used and stored with adequate precautions? |
Picric Acid must be used and stored in accordance with the Handling Picric Acid guidelines and Hazard Control Plan. |
High |
|
|
Are all chemical containers properly labeled? |
Containers holding hazardous materials, or whose contents could be mistaken for hazardous materials, must be labeled with the identity of the contents in English. |
Medium |
Label all chemical containers in accordance with the Label Chemical Containers guidelines on Chemical Storage and Inventory. |
|
Is a complete chemical abbreviation list posted when abbreviations are used on chemical containers? |
A complete chemical abbreviation list must be prominently posted in the lab (include common substances, extended as necessary with lab-specific abbreviations) when abbreviations are used on labels for chemicals. |
Low |
Refer to the Label Chemical Containers section on the "Chemical Storage and Inventory" page to get started. |
|
Are chemical storage cabinets labeled correctly? |
Label storage cabinets (and tubs) by compatibility group. For example, cabinets should be labeled with their appropriate hazard classification, such as corrosive, flammable, etc. |
Low |
|
|
Are incompatible chemicals segregated from each other? |
Chemicals must be separated and stored by compatibility group. Separation can include separate cabinets or in appropriate tubs/secondary containers. |
Medium |
|
|
Are chemical containers corrosion-free and/or not physically compromised or visibly contaminated? |
Chemical containers need to be free of corrosion/degradation, not physically compromised, and free of visible contamination. Secure contents and replace container. Follow hazardous waste policies and store all containers in accordance with guidelines from Chemical Storage and Inventory. |
Medium |
|
|
Is the carcinogen work/storage area posted? |
Storage and work areas where carcinogens are used must be designated with the "Carcinogen" label. Carcinogen stickers/labels can be requested from the EH&S Research Assistance Program ehsrap@ucsd.edu. |
Low |
Review Hazard Control Plan: Carcinogens for defining criteria of carcinogens and other guidelines. |