Skip to main content

System Status: 

Electrical Safety Guidelines

Reduce the possibility of fire or electrical shock by keeping your workplace free from electrical hazards.

Serious fire and shock hazards can result when electrical equipment is not maintained or used properly.

Wall outlets

A wall outlet is designed to provide for two electrical receptacles, leaving you room to plug in two devices or appliances. Adding cube adapters or wall taps to add additional outlets will overload the circuit and could result in a fire. Cube adapters or wall taps are prohibited.   

  • Contact Facilities Management (FM) to discuss the installation of more outlets if needed. 

  • Report broken outlets or missing cover plate to FM and do not use the outlet until repaired.  

  • Replace damaged extension cords — do not tape over a damaged cord.

  • Stress can occur where the electrical cord attaches to the cord plug. This stress will cause cracks and separations on the outer insulation and eventually a separation of the internal wires which will lead to a shock or fire hazard.

  • Ground-fault circuit interrupter (GFCI) protection is required for equipment used within 6 feet of sinks or in wet environments. Contact FM to install GFCI (858) 534-2930. 

  • Do not use outlet adaptors — they can cause the circuit to become overloaded. Multi-plug adapters, such as cube adapters or unfused plug strips, are prohibited in UC San Diego facilities.

  • Extension cords are only allowed for temporary use — they may only serve one portable appliance, must be plugged directly into an outlet and must be able to carry enough amperage to run the appliance they are connected to.outlet

  • Improper use of extension cords and outlet adaptors can present a serious fire safety hazard in the workplace. Non-home electrical fires represented 13% of total 2007-2011 non-home structure fires, 5% of associated civilian deaths, 13% of associated civilian injuries, and 21% of associated direct property damage (National Fire Protection Association). The most common cause of fires from extension cords is improper use and/or overloading, especially when the cord has multiple outlets. 
  • High-draw electrical appliances must be plugged directly into outlets(e.g., microwave ovens, space heaters, toasters/toaster ovens, and coffee makers.) These types of appliances typically draw large amounts of electricity and create fire risks when improperly plugged.

Learn more about electrical safety risks and see if your area might be at risk. Contact the following groups if you need professional help with electrical issues:

  • Residential buildings, contact the Housing Maintenance Customer Service Center, (858) 534-2600.
  • All other campus facilities, contact the Facilities Management Service Referral Desk, (858) 534-2930.
  • UC San Diego Medical Center facilities, contact:
    • Hillcrest: Facilities Engineering Help Desk, (619) 543-6454
    • Thornton Hospital: Facilities Engineering Help Desk, (858) 657-6400

Power strips (circuited power taps)

A circuited multiple-outlet power tap may be used if you need to increase electrical supply in your area. These devices have an internal circuit-breaker switch that will stop electrical flow if overloading occurs.

Guidelines for Use of Power Strips

Use only surge protectors or power strips that are “listed” by UL (Underwriters Laboratory) or ELT (Electrical Testing Laboratories). According to the UL listing, instructions for using a power tap includes:

power strip
  • Intended to be directly connected to a permanently installed receptacle;
  • Not intended to be series connected (daisy chained) to other relocatable power taps or to extension cords;
  • Not intended for use at construction sites and similar locations;
  • Not intended to be permanently secured to building structures, tables, work benches or similar structures, nor are they intended to be used as a substitute for fixed wiring; and
  • The cords are not intended to be routed through walls, windows, ceilings, floors or similar openings.

Although relocatable power taps are allowed, use them safely and properly. Check to be certain the markings are readily visible on the back of the strip indicating the name of the manufacturer and testing laboratory used. Power strips are designed for use with small appliances and business machines, do not plug in heavy appliances with high-powered loads. Visually inspect all power strips regularly to ensure they are not pinched, crushed or damaged in any way. If a power strip becomes hot to the touch, unplug it and consult a licensed professional.  

Get professional help with electrical issues:

  • Residential buildings, contact the Housing Maintenance Customer Service Center, (858) 534-2600.
  • All other campus facilities, contact the Facilities Management Service Referral Desk, (858) 534-2930.
  • UC San Diego Medical Center facilities, contact:
    • Hillcrest: Facilities Engineering Help Desk, (619) 543-6454
    • Thornton Hospital: Facilities Engineering Help Desk, (858) 657-6400

Extension cords

Extension cords are intended for temporary use, not for supplying permanent power to tools and appliances. If you must use an extension cord, do the following:

  • Select the right extension cord.
    • Answer these 3 questions about the intended use to determine the type, wire size, and length of cord needed for the job:
      1. Is the cord for indoor or outdoor use?
        • Cords rated for outdoor use can be used both indoors and out, but never use an indoor cord outside.
      2. How much electrical current (typically rated in amperes, or amps) does the tool or appliance require? The amperage requirement determines the wire size needed.
        • Choose the right wire size for the intended use. Extension cords are rated by wire size, known as gauge. The thicker the wire, the more amps it will carry. Amperage requirements are usually given with the tool or appliance.
        • A cord's wire thickness is identified by the letters AWG followed by numbers; typically 12, 14, or 16.
          Wire sample

          On this extension cord, the AWG 12-3 means the wire gauge is 12 and there are 3 wires inside.

          In this case, less is more – the lower the number, the thicker the wire.
        • Be sure the diameter of the extension cord is as large or larger than the cord being plugged into it.
      3. What is the maximum distance the cord will need to extend from the permanent electrical outlet?
        • Select the right length of cord. The ability of a wire to carry a specific amperage will diminish as its length increases. If you need a lot of amps carried over a long distance, you'll need a heavier gauge wire.
        • Use the chart below as a guide for selecting an extension cord of appropriate gauge and length for the amperage required.

    Chart for selecting an extension cord of appropriate gauge and length for the amperage required
    Ext.
    cord
    length
    Amperage required
    0-2
    amps
    2-5
    amps
    5-7
    amps
    7-10
    amps
    10-12
    amps
    12-15
    amps
    25 ft. 16 ga. 16 ga. 16 ga. 16 ga. 14 ga. 14 ga.
    50 ft. 16 ga. 16 ga. 16 ga. 14 ga. 14 ga. 12 ga.
    100 ft. 16 ga. 16 ga. 14 ga. 12 ga. 12 ga. 10 ga.
    150 ft. 16 ga. 14 ga. 12 ga. 12 ga. 10 ga.
    200 ft. 14 ga. 14 ga. 12 ga. 10 ga.
  • Inspect extension cords periodically for cracked or frayed insulation.
    • Replace cords that show signs of wear. Do not tape over them.
    • Buy UL-listed cords.
  • Do not link or "daisy chain" extension cords. Select a single extension cord long enough to do the job.
  • Plug extension cords directly into the wall, not into a power strip or 3-prong adaptor.
  • Never run an extension cord under carpeting or through walls.
  • Never tack or staple an extension cord to the wall or woodwork — it could damage the cord and create a fire hazard.

Electrical panels

Electrical panels house the circuit breakers that control each electrical outlet. Make sure power can be shut off quickly in case of emergency by doing the following:

  • Maintain 30-inch clearance in front of all electrical panels.
  • Label each circuit breaker, identifying the outlet it controls.
  • Keep access to electrical panels free of obstructions. Electrical panels must have 36" of clear floor space in all directions.

Electrical shock hazards

Electricity travels in closed circuits and wants to reach the ground any way it can. If you contact electricity, you become its conduit to the ground.

  • Be aware of situations where you may act as a circuit ground when working near electricity.
  • Never work on a "hot" (energized) circuit or electrical apparatus.
  • If any of these warnings occurs, take it seriously. Disconnect power and have the equipment serviced.
    • Mild shock or tingling when in contact with an electrical machine
    • Frayed or exposed wires
    • Excessively hot motors
    • Unusual odors such as burning insulation
    • Inoperative or erratic switches; erratic equipment operation
    • Sparks or smoke
For more information, contact EH&S Fire & Life Safety, (858) 534-3659.